CTC760E CT Analyzer (Variable frequency method)

 CTC760E Instrument transformer analyzer can carry out a series of standard tests quickly, such as determining the magnetization characteristic, saturation behavior (ALF/FS), transformation ratio and its accuracy, polarity, load, winding resistance, or remanence. Tests are performed in accordance with standards: IEC60044-1, IEC60044-6, IEC 61869, ANSI/IEEE C57.13.1.

描述
l  Use direct current method and variable frequency method (low frequency method) testing CT

excitation characteristic below 80KV, working fast.

l  Use both “voltage method” (through secondary injection) testing current transformer ratio and polarity (include

transformer bushing CTs).

l  Built-in power supply has an output current mode. Can use current method test current transformer ratio, polarity and check the integrity of the CT secondary circuit.

l  Output up to 200A with external current booster (option)

l  Test current transformer secondary winding DC resistance.

l  Test current transformer secondary circuit burden.

l  Test voltage transformer excitation characteristic, ratiopolarity and secondary winding DC resistance.

l  Draw the excitation curve and calculating the knee point accordance to IEC60044-1 and IEC60044-6.

l  Draw 5%, 10% CT error curve.

l  Measure CT’s ratio error and phase displacement.

l  Measure CT’s remanence factor (Kr), magnetizing inductance (Lm), secondary loop time constant (Ts), transient dimensioning factor (Ktd), peak instantaneous error (PIE), accuracy limit factor (ALF), instrument security factor (FS).

l  Draw current transformer Hysteresis loop curve

l  Transparent display shows values and curve clearly both indoor and outdoor.

l  High speed thermal printer can print values and curve.

l  Check the connecting cable automatically. Wrong connecting warning instructions.

l  Built-in large memory storage can store 20000 winding test values, loss of power without loss of values.

l  Use a USB flash drive to transfer the values to PC, and generate report.

l  Use a USB flash drive to update software.
  1. Output Voltage: 0~360V AC
  2. Output Current: 0~10Arms, peak 20A
  3. External Current Booster Output Current: 0~200A AC
  4. External Current Booster Output Current Duration: 8min at 150A
  5. Output Power: 0~3600VA
  6. Secondary Voltage Measurement Range: 2~360V AC
  7. Secondary Voltage Measurement Accuracy: ±(0.1%U+20mV)
  8. Primary Voltage Measurement Range: 0~20V AC
  9. Output Current Measurement Range: 0.01~10A AC
  10. Output Current Measurement Accuracy: ±(0.1%I+2mA)
  11. Secondary Current Measurement Range: 0~5A AC
  12. Secondary Current Measurement Accuracy: ±(0.1%I+2mA)
  13. Winding Resistance Measurement Range: 0~300Ω, resolution 1mΩ
  14. Winding Resistance Measurement Accuracy: ±(0.1%R+1mΩ)
  15. AC Load Measurement: 0~1000VA, resolution 0.001VA
  16. Transformation Ratio Measurement Range: 1~35000
  17. Rated Current Transformation Ratio Error: ±0.1% for 1~5000; ±0.2% above 5000
  18. Rated Current Phase Error: 3min at cosφ=0.8~1, resolution 0.1min
  19. Power Supply: 198~264V AC, 47~63Hz
  20. Operating Conditions: Temperature -10℃~50℃, Humidity ≤90%RH, non-condensing
  21. Main Unit Dimensions: 427×357×193mm
  22. Main Unit Weight: 11kg
  23. Current Booster Dimensions: 327×282×218mm
  24. Current Booster Weight: 12k
hdownload