CTC760E CT Analyzer (Variable frequency method)
CTC760E Instrument transformer analyzer can carry out a series of standard tests quickly, such as determining the magnetization characteristic, saturation behavior (ALF/FS), transformation ratio and its accuracy, polarity, load, winding resistance, or remanence. Tests are performed in accordance with standards: IEC60044-1, IEC60044-6, IEC 61869, ANSI/IEEE C57.13.1.
描述
l Use direct current method and variable frequency method (low frequency method) testing CT
excitation characteristic below 80KV, working fast.
l Use both “voltage method” (through secondary injection) testing current transformer ratio and polarity (include
transformer bushing CTs).
l Built-in power supply has an output current mode. Can use current method test current transformer ratio, polarity and check the integrity of the CT secondary circuit.
l Output up to 200A with external current booster (option)
l Test current transformer secondary winding DC resistance.
l Test current transformer secondary circuit burden.
l Test voltage transformer excitation characteristic, ratio, polarity and secondary winding DC resistance.
l Draw the excitation curve and calculating the knee point accordance to IEC60044-1 and IEC60044-6.
l Draw 5%, 10% CT error curve.
l Measure CT’s ratio error and phase displacement.
l Measure CT’s remanence factor (Kr), magnetizing inductance (Lm), secondary loop time constant (Ts), transient dimensioning factor (Ktd), peak instantaneous error (PIE), accuracy limit factor (ALF), instrument security factor (FS).
l Draw current transformer Hysteresis loop curve
l Transparent display shows values and curve clearly both indoor and outdoor.
l High speed thermal printer can print values and curve.
l Check the connecting cable automatically. Wrong connecting warning instructions.
l Built-in large memory storage can store 20000 winding test values, loss of power without loss of values.
l Use a USB flash drive to transfer the values to PC, and generate report.
l Use a USB flash drive to update software.
Output Voltage: 0~360V AC
Output Current: 0~10Arms, peak 20A
External Current Booster Output Current: 0~200A AC
External Current Booster Output Current Duration: 8min at 150A
Output Power: 0~3600VA
Secondary Voltage Measurement Range: 2~360V AC
Secondary Voltage Measurement Accuracy: ±(0.1%U+20mV)
Primary Voltage Measurement Range: 0~20V AC
Output Current Measurement Range: 0.01~10A AC
Output Current Measurement Accuracy: ±(0.1%I+2mA)
Secondary Current Measurement Range: 0~5A AC
Secondary Current Measurement Accuracy: ±(0.1%I+2mA)
Winding Resistance Measurement Range: 0~300Ω, resolution 1mΩ
Winding Resistance Measurement Accuracy: ±(0.1%R+1mΩ)
AC Load Measurement: 0~1000VA, resolution 0.001VA
Transformation Ratio Measurement Range: 1~35000
Rated Current Transformation Ratio Error: ±0.1% for 1~5000; ±0.2% above 5000
Rated Current Phase Error: 3min at cosφ=0.8~1, resolution 0.1min
Power Supply: 198~264V AC, 47~63Hz
Operating Conditions: Temperature -10℃~50℃, Humidity ≤90%RH, non-condensing
Main Unit Dimensions: 427×357×193mm
Main Unit Weight: 11kg
Current Booster Dimensions: 327×282×218mm
Current Booster Weight: 12k